Input/Output Interface

  • Buttons: Reset button
  • Digital Input Channels: 16
  • Isolation: 3k VDC or 2k Vrms

Digital Inputs

  • Connector: Screw-fastened Euroblock terminal
  • Counter Frequency: 2.5 kHz
  • Digital Filtering Time Interval: Software configurable
  • Dry Contact: On: short to GND Off: open
  • I/O Mode: DI or event counter
  • Points per COM: 8 channels
  • Sensor Type: Dry contact Wet Contact (NPN or PNP)
  • Wet Contact (DI to COM): On: 10 to 30 VDC Off: 0 to 3 VDC

LED Interface

  • LED Indicators: PWR, RDY, P1, P2

Serial Interface

  • Baudrate: 1200 bps to 921.6 kbps
  • Connector: Terminal block
  • No. of Ports: 2
  • Parity: None Even Odd
  • Pull High/Low Resistor for RS-485: 1 kilo-ohm, 150 kilo-ohms
  • Serial Standards: RS-485
  • Stop Bits: 1, 2
  • Surge: 1 kV
  • ESD: 15 kV
  • Data Bits: 8
  • Flow Control: None XON/XOFF

Serial Signals

  • RS-485-2w: Data+, Data-, GND

Serial Software Features

  • Industrial Protocols: Modbus RTU Server (slave)

Power Parameters

  • Power Connector: Screw-fastened Euroblock terminal
  • No. of Power Inputs: 1
  • Input Voltage: 12 to 48 VDC
  • Power Consumption: 154 mA @ 24 VDC

Physical Characteristics

  • Housing: Plastic
  • Dimensions: 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)
  • Weight: 200 g (0.44 lb)
  • Installation: DIN-rail mounting Wall mounting
  • Wiring: I/O cable, 16 to 26 AWG Power cable, 12 to 24 AWG

Environmental Limits

  • Operating Temperature: -10 to 75°C (14 to 167°F)
  • Storage Temperature (package included): -40 to 85°C (-40 to 185°F)
  • Ambient Relative Humidity: 5 to 95% (non-condensing)
  • Altitude: Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
  • Altitude: Please contact Moxa if you require products guaranteed to function properly at higher altitudes.

Standards and Certifications

  • EMC: EN 55032/24
  • EMI: CISPR 32, FCC Part 15B Class A
  • EMS: IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m IEC 61000-4-4 EFT: Power: 0.5 kV IEC 61000-4-5 Surge: Power: 2 kV IEC 61000-4-6 CS: 3 V IEC 61000-4-8 PFMF
  • Safety: UL 508
  • Shock: IEC 60068-2-27
  • Vibration: IEC 60068-2-6

Declaration

  • Green Product: RoHS, CRoHS, WEEE

MTBF

  • Time: 1,239,293 hrs
  • Standards: Telcordia SR332

Warranty

  • Warranty Period: 5 years
  • Details: See www.moxa.com/warranty

Available Models

Model No. Description Quantity
ioLogik R1210 Universal I/O, 16 DIs, -10 to 75°C operating temperature
ioLogik R1214 Universal I/O, 6 DIs, 6 relays, -10 to 75°C operating temperature
ioLogik R1212 Universal I/O, 8 DIs, 8 DIOs, -10 to 75°C operating temperature
ioLogik R1240 Universal I/O, 8 AIs, -10 to 75°C operating temperature
ioLogik R1241 Universal I/O, 4 AOs, -10 to 75°C operating temperature
ioLogik R1212-T Universal I/O, 8 DIs, 8 DIOs, -40 to 85°C operating temperature
ioLogik R1240-T Universal I/O, 8 AIs, -40 to 85°C operating temperature
ioLogik R1210-T Universal I/O, 16 DIs, -40 to 85°C operating temperature
ioLogik R1214-T Universal I/O, 6 DIs, 6 relays, -40 to 85°C operating temperature
ioLogik R1241-T Universal I/O, 4 AOs, -40 to 85°C operating temperature