Technolec

IOLOGIK E1200 SERIES

Universal I/O, 4 AIs, 4 DIs, 4 DIOs, -40 to 75°C operating temperature
iologik-e1200-series
User-definable Modbus TCP Slave addressing
Supports EtherNet/IP Adapter mode Requires online registration (available free of charge)
Supports RESTful API for IIoT applications
2-port Ethernet switch for daisy-chain topologies
Saves time and wiring costs with peer-to-peer communications
Active communication with MX-AOPC UA Server
Supports SNMP v1/v2c
Easy mass deployment and configuration with ioSearch utility
Friendly configuration via web browser
Simplifies I/O management with MXIO library for Windows or Linux
Class I Division 2, ATEX Zone 2 certification Class I Division 2 and ATEX currently do not apply to the E1213/E1213-T models.
Wide operating temperature models available for -40 to 75°C (-40 to 167°F) environments

Input/Output Interface

  • Analog Input Channels: 4
  • Configurable DIO Channels (by jumper): 4
  • Digital Input Channels: 4
  • Isolation: 3k VDC or 2k Vrms
  • Buttons: Reset button

Digital Inputs

  • Connector: Screw-fastened Euroblock terminal
  • Counter Frequency: 250 Hz
  • Digital Filtering Time Interval: Software configurable
  • Dry Contact: On: short to GND Off: open
  • I/O Mode: DI or event counter
  • Points per COM: 4 channels
  • Sensor Type: Dry contact Wet contact (NPN or PNP)
  • Wet Contact (DI to COM): On: 10 to 30 VDC Off: 0 to 3 VDC

Digital Outputs

  • Connector: Screw-fastened Euroblock terminal
  • Current Rating: 200 mA per channel
  • I/O Mode: DO or pulse output
  • I/O Type: Sink
  • Over-Current Protection: 2.6 A per channel @ 25°C
  • Over-Temperature Shutdown: 175°C (typical), 150°C (min.)
  • Over-Voltage Protection: 35 VDC
  • Pulse Output Frequency: 500 Hz (max.)

Analog Inputs

  • Accuracy: ±0.1% FSR @ 25°C ±0.3% FSR @ -10 to 60°C ±0.5% FSR @ -40 to 75°C
  • Built-in Resistor for Current Input: 120 ohms
  • Connector: Screw-fastened Euroblock terminal
  • I/O Mode: Voltage/Current
  • I/O Type: Differential
  • Input Impedance: 10 mega-ohms (min.)
  • Input Range: 0 to 10 VDC 0 to 20 mA 4 to 20 mA 4 to 20 mA (with burn-out detection)
  • Resolution: 16 bits
  • Sampling Rate: 12 samples/sec per module (shared between up to 4 channels)

Ethernet Interface

  • 10/100BaseT(X) Ports (RJ45 connector): 2, 1 MAC address (Ethernet bypass)
  • Magnetic Isolation Protection: 1.5 kV (built-in)

Ethernet Software Features

  • Configuration Options: Web Console (HTTP), Windows Utility (ioSearch), MCC Tool
  • Industrial Protocols: Modbus TCP Server (Slave), Moxa AOPC (Active Tag), MXIO Library, EtherNet/IP Adapter
  • Management: RESTful API, SNMPv1/v2c, SNMPv1 Trap, HTTP, DHCP Client, BOOTP, IPv4, TCP/IP, UDP
  • MIB: Device Settings MIB
  • Security: Access control list

LED Interface

  • LED Indicators: Power, Ready, Port 1, Port 2

Modbus TCP

  • Functions Supported: 1, 2, 3, 4, 5, 6, 15, 16, 23
  • Mode: Server (Slave)
  • Max. No. of Client Connections: 10

EtherNet/IP

  • Mode: Adapter
  • Max. No. of Scanner Connections: 9 (for read-only), 1 (for read/write)

Power Parameters

  • Power Connector: Screw-fastened Euroblock terminal
  • No. of Power Inputs: 1
  • Input Voltage: 12 to 36 VDC
  • Power Consumption: 139 mA @ 24 VDC

Physical Characteristics

  • Housing: Plastic
  • Dimensions: 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)
  • Weight: 200 g (0.44 lb)
  • Installation: DIN-rail mounting, Wall mounting
  • Wiring: I/O cable, 16 to 26 AWG Power cable, 12 to 24 AWG

Environmental Limits

  • Operating Temperature: -40 to 75°C (-40 to 167°F)
  • Storage Temperature (package included): -40 to 85°C (-40 to 185°F)
  • Ambient Relative Humidity: 5 to 95% (non-condensing)
  • Altitude: 4000 m
  • Altitude: Please contact Moxa if you require products guaranteed to function properly at higher altitudes.

Standards and Certifications

  • EMC: EN 55032/24, EN 61000-6-2/-6-4
  • EMI: CISPR 32, FCC Part 15B Class A
  • EMS: IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV IEC 61000-4-6 CS: 10 V IEC 61000-4-8 PFMF
  • Hazardous Locations: ATEX, Class I Division 2
  • Safety: UL 508
  • Shock: IEC 60068-2-27
  • Freefall: IEC 60068-2-32
  • Vibration: IEC 60068-2-6

Declaration

  • Green Product: RoHS, CRoHS, WEEE

MTBF

  • Time: 502,210 hrs
  • Standards: Telcordia SR332

Warranty

  • Warranty Period: 5 years
  • Details: See www.moxa.com/warranty

Security Functions

  • Authentication: Local database

Available Models

Model No. Description Quantity
ioLogik E1210-T Universal I/O, 16 DIs, -40 to 75°C operating temperature
ioLogik E1212-T Universal I/O, 8 DIs, 8 DIOs, -40 to 75°C operating temperature
ioLogik E1214-T Universal I/O, 6 DIs, 6 relays, -40 to 75°C operating temperature
ioLogik E1241-T Universal I/O, 4 AOs, -40 to 75°C operating temperature
ioLogik E1211-T Universal I/O, 16 DOs, -40 to 75°C operating temperature
ioLogik E1213-T Universal I/O, 8 DIs, 4 DOs, 4 DIOs, -40 to 75°C operating temperature
ioLogik E1211 Universal I/O, 16 DOs, -10 to 60°C operating temperature
ioLogik E1213 Universal I/O, 8 DIs, 4 DOs, 4 DIOs, -10 to 60°C operating temperature
ioLogik E1240-T Universal I/O, 8 AIs, -40 to 75°C operating temperature
ioLogik E1242-T Universal I/O, 4 AIs, 4 DIs, 4 DIOs, -40 to 75°C operating temperature
ioLogik E1240 Universal I/O, 8 AIs, -10 to 60°C operating temperature
ioLogik E1242 Universal I/O, 4 AIs, 4 DIs, 4 DIOs, -10 to 60°C operating temperature
ioLogik E1210 Universal I/O, 16 DIs, -10 to 60°C operating temperature
ioLogik E1212 Universal I/O, 8 DIs, 8 DIOs, -10 to 60°C operating temperature
ioLogik E1214 Universal I/O, 6 DIs, 6 relays, -10 to 60°C operating temperature
ioLogik E1241 Universal I/O, 4 AOs, -10 to 60°C operating temperature
ioLogik E1262 Universal I/O, 8 TCs, -10 to 60°C operating temperature
ioLogik E1260 Universal I/O, 6 RTDs, -10 to 60°C operating temperature
ioLogik E1262-T Universal I/O, 8 TCs, -40 to 75°C operating temperature
ioLogik E1260-T Universal I/O, 6 RTDs, -40 to 75°C operating temperature