Technolec

IOPAC 8500 SERIES (85M) MODULES

Module for the ioPAC 8500/8600 Series, 16 DIs, 24 VDC, sink/source, -40 to 75°C operating temperature
iopac-8500-series-85m-modules
Compliant with EN 50121-3-2, EN 50121-4, and a portion of EN 50155 specifications
Rugged and compact design for harsh environments
Expand the I/O and communication capabilities of your ioPAC 8600 or 8500 Series device
Wide operating temperature range: -40 to 75°C (-40 to 167°F)
Millisecond timestamp granularity for digital input and analog input
Supports sampling rates up to 40 kHz for analog input
Pre-recording for analog input data logging
Up to 4 3-in-1 RS-232/422/485 serial ports

Input/Output Interface

  • Digital Input Channels: 16
  • Isolation: 3k VDC or 2k Vrms

Digital Inputs

  • Voltage: 24 VDC
  • Connector: Spring-type Euroblock terminal
  • Counter Frequency: 5 kHz
  • Dry Contact: On: short to GND Off: open
  • I/O Mode: DI, event counter, or frequency
  • Points per COM: 8 channels
  • Sensor Type: Dry contact Wet Contact (NPN or PNP)
  • Wet Contact (DI to COM): On: 10 to 30 VDC Off: 0 to 3 VDC

Digital Outputs

  • Pulse Output Frequency: 5 kHz

Power Parameters

  • Power Consumption: 50.0 mA @ 24 VDC

Physical Characteristics

  • Dimensions: 25 x 128.2 x 85.5 mm (0.98 x 5.05 x 3.37 in)
  • Weight: Under 80 g
  • Wiring: I/O cable, 14 to 28 AWG

Environmental Limits

  • Operating Temperature: -40 to 75°C (-40 to 167°F)
  • Storage Temperature (package included): -40 to 85°C (-40 to 185°F)
  • Ambient Relative Humidity: 5 to 95% (non-condensing)
  • Altitude: 2000 m Note: Please contact Moxa if you require products guaranteed to function properly at higher altitudes.

Standards and Certifications

  • EMC: EN 55032/24 EN 61000-6-2/-6-4
  • EMI: CISPR 32, FCC Part 15B Class A
  • EMS: IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV IEC 61000-4-3 RS: 5100 MHz to 6000 MHz: 3 V/m IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV IEC 61000-4-6 CS: 10 V IEC 61000-4-8 PFMF
  • Railway: EN 50121-4 EN 50155 (complies with a portion of EN 50155 specifications)
  • Safety: UL 508
  • Shock: IEC 60068-2-27
  • Vibration: IEC 60068-2-6

MTBF

  • Time: 1,132,561 hrs
  • Standards: Telcordia SR332

Warranty

  • Warranty Period: 5 years
  • Details: See www.moxa.com/warranty

Available Models

Model No. Description Quantity
85M-1602-T Module for the ioPAC 8500/8600 Series, 16 DIs, 24 VDC, sink/source, -40 to 75°C operating temperature
85M-3810-T Module for the ioPAC 8500/8600 Series, 8 AIs, 0 to 10 V, -40 to 75°C operating temperature
85M-3801-T Module for the ioPAC 8500/8600 Series, 8 AIs, 4 to 20 mA, 40 kHz, -40 to 75°C operating temperature
85M-6810-T Module for the ioPAC 8500/8600 Series, 8 TCs, -40 to 75°C operating temperature
85M-5401-T Module for the ioPAC 8500/8600 Series, 4-port serial, DB44 connectors, -40 to 75°C operating temperature
85M-3800-T Module for the ioPAC 8500/8600 Series, 8 AIs, 4 to 20 mA, -40 to 75°C operating temperature
85M-6600-T Module for the ioPAC 8500/8600 Series, 6 RTDs, -40 to 75°C operating temperature
85M-2600-T Module for the ioPAC 8500/8600 Series, 16 DOs, 24 VDC, sink, -40 to 75°C operating temperature
85M-3811-T Module for the ioPAC 8500/8600 Series, 8 AIs, 0 to 10 V, 40 kHz, -40 to 75°C operating temperature