IOPAC 6500 SERIES (65M) I/O MODULES
ioPAC 6500 DI module with 32 channels, 24 VDC, -40 to 75°C operating temperature, conformal coating
Error-proof design to prevent erroneous installations
Tool-free hardware installation and hot-swap design for maximizing operation efficiency
Fully modular design for maximum deployment flexibility
Tool-free hardware installation and hot-swap design for maximizing operation efficiency
Fully modular design for maximum deployment flexibility
Input/Output Interface
- Digital Input Channels: 32
- Isolation: 65M-3600-CT-T/65M-3610-CT-T/65M-4820-CT-T/65M-5801-CT-T:- Between signal and system: 3k VDC- Between groups: 1k VDC per minAll other models:- Between signal and system: 3k VDC
Digital Inputs
- I/O Type: Sink (Internal/external field circuit supply for dry contact)
- I/O Mode: DI or event counter (channels 1 to 8, group configurable by software)
- Internal Field Circuit Supply Voltage: 24 VDC 22.8 to 25.2 VDC
- Internal Field Circuit Supply Current: 125 mA (max.) (Only for dry contact)
- Input Voltage: On: 11 to 30 VDC Off: 0 to 5 VDC
- Input Current (voltage on): 2.35 mA ± 20% per channel
- Counter Frequency: Square wave: 0 to 10 kHz
- Digital Filtering Time Interval: Software configurable
- Diagnostics: Input Wire-break Detection (current: 50 µA max., delay: 20 ms) Internal Field Circuit Supply Detection (17.5 VDC, 16 to 19 VDC)
Digital Outputs
- I/O Type: Source
- I/O Mode: DO or pulse output (channel 1 to 8, group configurable by software)
- Common Power Input Voltage: 24 VDC 19.2 to 28.8 VDC
- Common Power Input Current: 6.4 A (max.)
- Load Current: 200 mA/channel (typ.) 500 mA/channel (max.)
- Pulse Duration: 500 μs
- Protection: Output Short-circuit Protection Common Power Input Over-voltage Protection Inductive Load Shutdown Voltage Protection
- Diagnostics: Wire Break Detection (on state, output current 3 mA) Wire Break Detection (off state, output load impedance > 58 kilo-ohms) Output Short-Circuit Detection (output current > 0.87 A, range: 0.64 to 1.2 A) External Power Detection (17.5 VDC, 16 to 19 VDC) Failsafe Configuration (hold last/failsafe state)
Analog Inputs
- I/O Mode: 65M-3600-CT-T: Current65M-3610-CT-T: Voltage65M-3800H-CT-T: HART
- I/O Type: Differential
- Input Range: 65M-3600-CT-T:0 to 20 mA 4 to 20 mA65M-3610-CT-T:0 to 10 V1 to 5 V65M-3800H-CT-T:4 to 20 mA
- Overload Permitted on Inputs: 65M-3600-CT-T: ±30 mA65M-3610-CT-T: ±12 V65M-3800H-CT-T: 30 mA
- Converter Resolution: 16 bits
- Measurement Resolution: 65M-3600-CT-T:2 μA (0 to 20 mA)1.6 μA (4 to 20 mA)65M-3610-CT-T:1 mV (0 to 10 V)0.4 mV (1 to 5 V)65M-3800H-CT-T: 1.6 μA (4 to 20 mA)
- Accuracy: ±0.1% FSR @ 25°C ±0.3% FSR @ -40 to 75°C
- Conversion Time: 100 ms
- Rejection Ratio: Normal mode: > 60 dB @ 60 Hz (min.), conversion time: 100 ms Common mode: > 90 dB @ 60 Hz (min.), conversion time: 100 ms
- Input Impedance: 65M-3800H-CT-T: 250 ohms65M-3600-CT-T: 250 ohms65M-3610-CT-T: 1 mega-ohms
- Diagnostics: 65M-3800H-CT-T:Input Wire-breakInput Short-circuitInput Underflow/Overflow Detection65M-3600-CT-T:Internal Loop Power Detection (17.5 VDA, 16 to 19 VDC)Input Short-circuit Detection65M-3600-CT-T (in 4 to 20 mA mode):Input Wire-break Detection (delay: 0.8 s)65M-3610-CT-T:Input Wire-break Detection (delay:1.6 s max)
Analog Outputs
- I/O Mode: Voltage/Current
- Output Range: 0 to 10 V1 to 5 V0 to 20 mA4 to 20 mA
- Converter Resolution: 16-bit
- Output Resolution: 1 mV (0 to 10 V) 0.4 mV (1 to 5 V) 2 μA (0 to 20 mA) 1.6 μA (4 to 20 mA)
- Accuracy: ±0.1% FSR @ 25°C ±0.3% FSR @ -40 to 75°C
- Output Refresh Time: 16 ms
- Output Impedance: Voltage mode: 1 kilo-ohms (min.) Current mode: 750 ohms (max.)
- Diagnostics: Output Short-circuit Detection (voltage) Failsafe Configuration (hold last/failsafe state) Output Wire-break Detection (current)
Serial Interface
- Serial Standards: RS-232, RS-422, RS-485-2w
- Baudrate: 300, 600, 1200, 1800, 2400, 4800, 9600, 19200, 38400, 57600, and 115200 bps
- Data Bits: 7, 8
- Stop Bits: 1, 2
- Parity: None Even Odd
- Flow Control: RTS/CTS, XON/XOFF
- Serial Signals: RS-232: TxD, RxD, RTS, CTS, GND RS-422: Tx+, Tx-, Rx+, Rx-, GND RS-485-2w: Data+, Data-, GND
Terminal Blocks
- Connector: Screw-fastened terminal block
- Dimensions: 42.3 x 102.38 x 80.8 mm (1.67 x 4.03 x 3.18 in)
- Weight: 164 g (0.36 lb)
Power Consumption
- System Power: 65M-1900-CT-T/65M-2901-CT-T:0.068 A @ 12 VDC65M-3610-CT-T/65M-4820-CT-T:0.069 A @ 12 VDC65M-3600-CT-T:0.073 A @ 12 VDC65M-3800H-CT-T: 0.072 A @ 12 VDC65M-5801-CT-T: 0.143 @ 12 VDC
- Field Power: 65M-1900-CT-T:0.019 A @ 24 VDC (without internal field circuit supply)0.115 A @ 24 VDC (32-channel dry contact with internal field circuit supply)65M-2901-CT-T:0.005 A @ 24 VDC65M-3600-CT-T:0.053 A @ 24 VDC (without internal loop power)0.466 A @ 24 VDC (16-channel 20 mA input with internal loop power)65M-3610-CT-T:0.038 A @ 24 VDC65M-3800H-CT-T:0.05 A (max.) @ 24 VDC (without internal loop power)0.25 A (max.) @ 24 VDC (8-channel 4 to 20 mA input with internal loop power all in 20 mA)0.66 A (max.) @ 24 VDC (500 mA input with internal loop power)65M-4820-CT-T:0.022 A @ 24 VDC (without external load)0.266 A @ 24 VDC (4-channel 20 mA output)65M-5801-CT-T: 0.11 A @ 24 VDC
Physical Characteristics
- Housing: Plastic
- Dimensions: 42 x 116 x 130 mm (1.65 x 4,57 x 5.12 in)
- Weight: 253 g (0.56 lb)
Environmental Limits
- Operating Temperature: -40 to 75°C (-40 to 167°F) Note: Proper airflow is required in an environment with temperature > 65°C.
- Storage Temperature (package included): -40 to 85°C (-40 to 185°F)
- Ambient Relative Humidity: 5 to 95% (non-condensing)
- Altitude: Up to 2000 meters
- Altitude: Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
Standards and Certifications
- EMC: EN 55032/35 EN 61000-6-2/-6-4
- EMI: CISPR 32, FCC Part 15B Class A
- EMS: IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m IEC 61000-4-4 EFT: Power: (DC) 1 kV; Signal: 1 kV IEC 61000-4-5 Surge: Power: (DC) 0.5 kV L-N, 1 kV L/N-PE; Signal: 1 kV; IO: 0.5 kV IEC 61000-4-6 CS: Power: (DC) 10 V; Signal: 10 Vrms IEC 61000-4-8 PFMF: 30 A/m
- Safety: UL 61010-1 UL 61010-2-201
- Shock: IEC 60068-2-27 Half sine wave; acceleration: 15 g; time: 11 ms
- Vibration: IEC 60068-2-6 DIN-rail mounted:7 mm peak-peak (p-p) (2 to 8.42 Hz), 1 g (8.42 to 150 Hz)Rack mounted (with optional kit):7 mm peak-peak (p-p) (2 to 8.42 Hz), 0.5 g (8.42 to 150 Hz)
MTBF
- Time: 2,057,118 hrs
- Standards: Telcordia Standard SR-332
Warranty
- Warranty Period: 5 years
- Details: See www.moxa.com/warranty