IOPAC 8600 SERIES (86M) MODULES

Module for the ioPAC 8600 Series with 8 DOs, 24 VDC, sink, channel-to-channel isolation, channel LED, -40 to 75°C operating temperature
iopac-8600-series-86m-modules
Complies with all EN 50155 mandatory test items This product is suitable for rolling stock railway applications, as defined by the EN 50155 standard. For a more detailed statement, click here: www.moxa.com/doc/specs/EN_50155_Compliance.pdf
Complies with EN 50121-4
Rugged and compact design for harsh environments
Expand the I/O and communication capabilities of your ioPAC 8600 Series device
Wide operating temperature range: -40 to 75°C (-40 to 167°F)
Channel-to-channel isolated digital input and output
24 to 110 V DI/O module and universal power input range module
Supports CAN bus for CAN 2.0 A/B communication

Input/Output Interface

  • Digital Output Channels: 8
  • Isolation: 3k VDC or 2k Vrms

Digital Outputs

  • Voltage: 24 VDC
  • Connector: Spring-type Euroblock terminal
  • Current Rating: 200 mA per channel
  • I/O Mode: DO or PWM
  • I/O Type: Sink
  • Over-Temperature Shutdown: 175°C (typical), 150°C (min.)
  • Over-Voltage Protection: 41 VDC
  • Pulse Output Frequency: 1 kHz
  • Short-Circuit Protection: 750 mA @ 25°C

Power Parameters

  • Power Consumption: 76.7 mA @ 24 VDC

Physical Characteristics

  • Dimensions: 25 x 128.2 x 85.5 mm (0.98 x 5.05 x 3.37 in)
  • Weight: Under 80 g
  • Wiring: I/O cable, 16 to 28 AWG

Environmental Limits

  • Operating Temperature: -40 to 75°C (-40 to 167°F)
  • Storage Temperature (package included): -40 to 85°C (-40 to 185°F)
  • Ambient Relative Humidity: 5 to 95% (non-condensing)
  • Altitude: 2000 m
  • Altitude: Please contact Moxa if you require products guaranteed to function properly at higher altitudes.

Standards and Certifications

  • EMC: EN 55032/24, EN 61000-6-2/-6-4
  • EMI: CISPR 32, FCC Part 15B Class A
  • EMS: IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV IEC 61000-4-3 RS: 5100 MHz to 6000 MHz: 3 V/m IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV IEC 61000-4-6 CS: 10 V IEC 61000-4-8 PFMF
  • Railway: EN 50121-4, EN 50155
  • Safety: UL 508
  • Shock: IEC 60068-2-27
  • Vibration: IEC 60068-2-6

MTBF

  • Time: 1,766,037 hrs
  • Standards: Telcordia SR332

Warranty

  • Warranty Period: 5 years
  • Details: See www.moxa.com/warranty

Available Models

Model No. Description Quantity
86M-2604D-T Module for the ioPAC 8600 Series, 6 Relays, form A (N.O.), channel LED, -40 to 75°C operating temperature
86M-5250-T Module for the ioPAC 8600 Series, 2 CAN ports, -40 to 75°C operating temperature
86M-2830D-T Module for the ioPAC 8600 Series with 8 DOs, 24 VDC, sink, channel-to-channel isolation, channel LED, -40 to 75°C operating temperature
86M-2821D-T Module for the ioPAC 8600 Series, 8 DOs, 24 to 110 VDC, source, channel LED, -40 to 75°C operating temperature
86M-1620D-T Module for the ioPAC 8600 Series, 16 DIs, 24 to 110 VDC, sink, channel LED, -40 to 75°C operating temperature
86M-4420-T Module for the ioPAC 8600 Series, 4 AOs, 0 to 10 V, -10 to 10 V, 0 to 20 mA, or 4 to 20 mA, -40 to 75°C operating temperature
86M-1832D-T Module for the ioPAC 8600 Series with 8 DIs, 24 VDC, sink/source, channel-to-channel isolation, channel LED, -40 to 75°C operating temperature
86M-5212U-T Module for the ioPAC 8600 Series, 2-port 2-wire Ethernet switch, -40 to 75°C operating temperature